PRODUCT PERFORMANCE INQUIRY (11-24-2009) PPI NUMBER: CUSTOMER: PRODUCT: CATALOG NUMBER: INITIATOR: 21061 Freeport Indonesia Hi*Lite XL Suspension 513213-1001/512213-1201 J.Rumble PPI INFORMATION ENTERED IN SYSTEM: 8/6/2009 MATERIAL AVAILABLE FOR EVALUATION: 11/3/2009 BACKGROUND Three Hi*Lite XL suspension insulators were returned by Freeport Indonesia for analysis. Of these, two insulators were catalog number 513213-1001 and one insulator was 512213-1201. The RGFS indicated that the insulators were installed in a service area with high humidity and mineral dust. INVESTIGATION / OBSERVATIONS Based on the number of weathersheds and the end fitting configuration it was confirmed that the returned insulators were catalog number 512213-1001 and 512213-1201. The catalog numbers also matched the markings on the CSR's on each insulator. The two insulators returned (catalog number 513213-1001) were marked as #282 and #230, whereas catalog number 512213-1201 was marked as tower 3 by the customer. The condition of the insulators at the time of return is listed below. Catalog Number 513213-1001 Sample Number #282 Condition at the time of return The insulator had signs of severe contamination; the polymer housing was covered with a brown residue. The first weathershed from line end had significant erosion extending through the weathershed to the sheath. Weathersheds #17, 19, 21, 33, 35 and 37 from line end also had some erosion. Serial number: 33796, indicates that the unit was made on 337th day of the year 1996. 513213-1001 #230 There was no visible damage to the insulator. One side of the insulator had some unknown black residue. The insulator appeared chalked. Serial number: 06497, indicates that the unit was made on 64th day of the year 1997. 512213-1201 Tower 3 The insulator was shipped with a line end ring attached. The ring was installed 1/4 " below the normal ring position. The insulator appeared chalked and the mid sections were covered with brown residue. There was no visible damage to the insulator. Serial number: 01497, indicates that the unit was made on 14th day of the year 1997. Table 1: Condition of returned insulators Page 1 of 6 This information is of a confidential nature and is not to be conveyed to any organization or individual other than those expressly approved by Hubbell Power Systems, Inc. Figure 1: Ground end sample#282 Figure 5: Contaminant on Sample#282 Figure 6: Contaminant on sample#230 Figure 2 Line end sample#282 Figure 7: Sample#230 Figure 3: Erosion on sample#282 Figure 8: Contaminant on sample Tower#3 Figure 4: Line end sample#282 Page 2 of 6 This information is of a confidential nature and is not to be conveyed to any organization or individual other than those expressly approved by Hubbell Power Systems, Inc. Figure 9: Sample#230 Figure 10: Ring assembled 0.25" below normal position An ESDD test was performed on sample # 282 to determine the level of contaminants / amount of salts present on the insulator. The ESDD (Equivalent Salt Deposit Density) test measures the soluble salts deposited on the surface of the insulator by washing that surface in a known volume of deionized (DI) water. The water’s conductivity is measured after the washing is complete. From the conductivity of a known volume of water and the surface area of the insulator washed, an average deposit density for NaCl can be calculated. This relative value can then be comparatively ranked. The ESDD values were calculated using the equations published in “APPLICATION GUIDE FOR INSULATORS IN A CONTAMINATED ENVIRONMENT “(IEEE F 77 639-8.) The equivalent salt quantity in the solution was calculated by the following equation. X (mg) =A*B*10 Where A is the quantity of DI water solution (ml) and B is the percentage equivalent salt concentration And the equivalent salt quantity per unit surface area Y (mg/cm2) is calculated by dividing the equivalent salt quantity in solution by the washed surface area of the insulator, S (cm 2) Y = X/S= (A*B*10)/S In this case A =920 ml, B=0.00150 % X= 920*.00150*10 X =13.8mg The surface area of each shed is approximately 27.46 in2 or 177.13 cm 2. For this test, 6 weathersheds were washed and the surface area was calculated as S= 177.13*6=1062.78 cm2 ESDD=Y= X/S = 13.8/1062.78 =.0129 mg/ cm2 The calculated ESDD value falls under the very light range (0.0 – 0.03 mg/cm2). Page 3 of 6 This information is of a confidential nature and is not to be conveyed to any organization or individual other than those expressly approved by Hubbell Power Systems, Inc. Sample On Test Sample# 282 Area Washed 6 sheds washed (middle of unit) Measured Ohm Cm Temp. Deg. F Temp. Correction Factor Corrected Temp. Resistivity Ohm Cm Soluti on In ML % NACL Area In Square Cm. 36231.9 70 1.065 38586.9 920 0.0015 1062.78 Mg/Cm Squared .0129 Table 2: ESDD on sample#282 Next all three returned samples were subjected to wet 60HZ flash over testing per ANSI C29.1. The results from the flashover tests are shown in the table below. Designation Bar. (cm Hg) Temp. Dry (°F) Rel. Hum. Unit 1 Sample# 282 73.8 65.8 41.2 kV (RMS) Uncorrected 1 2 3 4 5 6 7 8 9 10 Average ANSI C29.1 Corrected Unit 2 Sample# 230 73.8 65.8 41.2 kV (RMS) Uncorrected ANSI C29.1 Corrected Unit 3 Tower #3 73.8 65.8 41.2 kV (RMS) Uncorrected ANSI C29.1 Corrected 650* 655.3 650 655 650 655 630 635 655 660 620 625 650 655 650 655 610 614 640 645 640 645 640 645 590 594 650 655 655 660 640 645 585 589 650 655 620 625 640 645 610 614 650* 655.3 641 646.8 626.5 631.6 * Sample#282 could not be flashed over within the transformer limit of 650KV, so the sample was energized to 650KV and the voltage was held for 1 minute. Table 3: 60HZ wet Flashover Test Next the insulators were subjected to ultimate tensile load test. Samples marked #282 and 230 were rated for 50,000 lbs ultimate and sample marked tower#3 was rated for 30,000 lbs ultimate load. All three samples met the requirements. The table below shows the ultimate load and mode of failure for each sample. Sample# (Catalog#) SML (lbs) Ultimate Load (lbs) Mode of Failure 282 (513213-1001) 50,000 62,626 Crimp slip (ball fitting end) 230 (513213-1001) 50,000 50,823 Crimp slip (chain eye fitting) Tower#3 (512213-1201) 30,000 45,861 Crimp Slip (ball fitting end) Table 4: Ultimate tensile load test Page 4 of 6 This information is of a confidential nature and is not to be conveyed to any organization or individual other than those expressly approved by Hubbell Power Systems, Inc. Figure 11: Test Setup Figure 12: Test Setup Figure 13: Test Setup Figure 14: Crimp Slip (tower#3) Figure 15: Crimp Slip (sample#282) Figure 16: Crimp Slip (Sample#230) Page 5 of 6 This information is of a confidential nature and is not to be conveyed to any organization or individual other than those expressly approved by Hubbell Power Systems, Inc. ASSESSMENT / CONCLUSIONS The ESDD test performed on sample #282 indicated very light contamination. The ESDDs are also affected by environmental conditions around the time of removal of the insulator from service. Flashovers, rain and handling will all alter the level of contamination on the insulator and can give varying ESDD values. The erosion observed on sample #282 appears to be the result of heavy leakage current activity. With ESP, heavy leakage current activity can result in erosion of the base material. The polymer will not, under normal circumstances, track. The wet flashover test indicated that the flashover values are approximately 90% of the ratings of a new product (wet flashover for new product =720KV). The ultimate tensile load on all three insulators exceeded the SML. All three returned insulators appeared to have light chalking. Chalking results from exposure of the polymer to ultraviolet energy (UV). Within a discrete bandwidth, the UV energy has the potential to disrupt the molecular bonds in the backbone of the polymer molecules. If that occurs, the organic portions of the polymer ablate, leaving behind the inorganic filler, alumina tri-hydrate (ATH). The ATH appears as a white, chalky powder. Chalking will not affect the electrical performance of the insulators and will help to shield the underlying polymer from additional UV exposure. The erosion observed on sample#282 appears to have been caused by leakage current activity over an extended period of time. Also the overall appearance indicated that the service environment was severely contaminated. Any insulators with severe erosion to the polymer should be replaced at the earliest opportunity. If the erosion on the insulator extends to the core (exposing the fiberglass rod) then such insulators must be replaced immediately. The contaminant on the insulators could not be positively identified but based on the information from the RGFS it appears that it is mineral dust. Overall, all three insulators performed satisfactorily both electrically and mechanically. (Please note that, unless otherwise directed by the customer, it is our intent to dispose of the parts returned under this PPI after 03-1-2010) APPROVED BY: R. A. Bernstorf _____________________________________________ PRINCIPAL ENGINEER, INSULATORS John P. Lombardi ______________________________________________________ ADMINISTRATOR, QUALITY SYSTEMS Page 6 of 6 This information is of a confidential nature and is not to be conveyed to any organization or individual other than those expressly approved by Hubbell Power Systems, Inc.