2015 International Symposium on Lightning Protection (XIII SIPDA), Balneário Camboriú, Brazil, 28 th Sept. – 2nd Oct. 2015. Development of shield-type multi-chamber lightning arrester for 35kV OHL Streamer Electric Company, Saint-Petersburg, Russia [email protected] Podporkin, E.Yu. Enkin, V.V. Zhitenev, R.I. Zainalov, V.E. Pilshchikov, D.O. Belko. Abstract – the paper presents an alternative to the traditional method of lightning protection of 35 kV overhead lines based on shield-type multi-chamber arresters. The main stages of the design of arrester, and also shows the test results confirming compliance with required characteristics. second end of MCS is equipped with a rod lead directed upwards. а) Keywords—component; insulators-arresters, lightning protection, multi-chamber arresters, overhead power lines, power arc, multi-chamber system, direct lightning strike, arc interruption. I. 2 4 3 2 INTRODUCTION In order to ensure lightning protection of high-voltage overhead lines (OHL) for 35-220kV, multi-chamber insulator arresters (MCIA) [1] have been developed which are installed in place of the existing suspended insulation. However, in some cases replacement of insulation might be unreasonable or complicated. In view of the above a goal of development of multi-chamber arresters (MCA) for OHL protection has become urgent. These arresters will be installed in parallel to the protected insulation without its replacement. 4 4 2 1 c) The main working element of both MCIA and MCA being developed is a multi-chamber system (MCS) (Fig. 1). It contains a number of electrodes integrated in the profile of silicone rubber. Between the adjoining MCS electrodes cylindrical arc quenching chambers of specially designed configuration are molded. Spark gaps are formed inside the chambers. d) Fig. 1. Fragment of multi-chamber system: a) plan view; b) side view, initial stage of spark discharge; c) side view, last stage of spark discharge; d) discharge shaft cross-section, end view; 1 – silicon rubber profile; 2 – intermediate electrodes; 3 – arc suppression chambers; 4 – spark discharge channel. The arrester consists of two parts which look similar to toroidal shields (hereinafter are referred for short to as “shields" (see Fig. 2). Due to this, the arrester obtained its name: shield-type MCA for 35kV OHL (or SAd35z in the international market). 1 6 5 8 MCS’s are installed on a support structures made of insulation material. The shields are fastened by insulation rods to the upper and lower ends of the insulator string. 9 4 7 1 The upper shield is installed on the string strap, the lower one – on the eyelet. Shield to shield orientation can be changed in order to provide the required value of the spark gap between the tap leads. The shields support structures are manufactured of insulating material and integrated in MCS by means of hot moulding. It results in having a unified cast structure. 3 2 10 а) b) Fig. 2. SAd35z: a) general view; b) photograph of testing: The first end of the lower MCS shield, via spark gap and string mountings, is connected with line conductor, and the 978-1-4799-8754-2/15/$31.00 ©2015 IEEE 1 b) 1– upper and lower shields with MCS; 2 – lower incoming electrode; 3 – lower tap lead; 4 – intermediate tap leads; 5 – upper incoming electrode; 6 – traverse; 7 – conductor; 8 – insulator; 9, 10 – spark gaps. 88 Under the impact of voltage surge on the OHL conductor, for instance, in case of a direct lightning stroke on the conductor, the spark air spaces between the mountings and the lower MCS shield and between the rod electrodes of the upper and lower shields and MCS’s of both shields will be activated. The current caused by lightning-caused overvoltage flows from the conductor through the spark discharge gap of the lower shield, and further through the MCS of this shield, discharge gap between the intermediate tap leads, through the MCS of the upper shield, along its metal rod, the tower and goes to the ground (Fig. 2b) TABLE 1. SAD35Z TESTING PROGRAM No. Electrical tests At MCS operation sequential breakdown of spark gaps in each arc quenching chamber occurs with formation of conducting plasma channels (Fig. 1 a,b). Further on, under the impact of applied voltage the current starts increasing in the chambers. It causes heating of the arc channel, increase of its diameter and, as a consequence, pressure increase inside the chambers with arc carry-over from the discharge gap (Fig. 1 c,d). Arc effluence causes its elongation, displacement in cold air, cooling and increase of channel electrical resistance. 1 Checking of arrester coordination with insulation in dry and rain condition in case of voltage surge with a steep leading edge. 2 Power frequency voltage withstand test in dry and rain conditions. 3 Determination of 50% discharge characteristics under the impact of lightning impulses of standard shape 1.2/50 μs. 4 Power Arc Follow (PAF) current quenching test. 5 Measuring of industrial radio interference level. Climatic tests Contact of the arc with chamber walls causes silicon rubber evaporation (ablation). In addition to pressure increase it modifies the chemical composition of the discharge. During evaporation the silicon rubber (C2H6SiO)n adds therein the components with high output activity (for instance, for hydrogen H 13.6 eV) reducing the discharge channel conductivity. 6 Impact of ambient temperature change 7 Salt fog test 8 Accelerated weathering test (IEC 62217) Mechanical tests 9 Withstanding load 10 Vibration resistance test III. Impact of all these factors causes restoration of the discharge gap electrical strength upon the follow current zero crossing and prevents repetitive arc ignition. DEVELOPMENT OF ARRESTER DESIGN Diameter of SAd35z shield is selected based on the requirement to install thereon the required number of MCS discharge chambers capable to ensure stable quenching of the PAF current with the specified greed voltage applied. It is worth mentioning that the capability of arc quenching chambers to displace the arc outside MCS allows dispersing most of follow current energy in the ambient space. This makes the design of MCS resistant to electrodynamic and thermal impacts of the direct lightning strike surge current and the follow current arc. II. Types of inspections and tests SAd35z is intended for lightning protection of OHL 35kV with insulated neutral or neutral grounded with resistance at the substations. In both cases single-phase short circuit current is significantly less than in case of phase-to-phase short circuit. Due to this the case of phase-to-phase short circuit is the defining one. Overvoltage occurring on the conductors of OHL 35kV due to the lightning discharge effect may cause a simultaneous operation of two SAd35z arresters of different phases. The maximum operating line voltage in the 35kV grid is Um.o.l= 35х1.15= 40.3 kVeff. (effective value). It is equally divided between two arresters. Because of that each SAd35z should ensure interruption of the follow current arc with 20.2 kVeff voltage, and one shield – with 10.1 kVeff voltage. GENERAL MISSION STATEMENT In the development of SAd35z it is necessary to resolve several electrical engineering and design problems. Electrical characteristics of the arrester should ensure reliable coordination with the protected insulation and let it quench the follow current caused power arc in case of any lightning impact, including direct lightning strikes to the phase conductor, backflashovers and induced overvoltrages. The arrester should have a resistance to long-term weather exposure (temperature, humidity, solar radiation), as well as to mechanical impacts of wind and ice loads under low ambient temperatures. The length of spark gap between the shield tap leads (see Fig. 2) should ensure insulation protection by coordinated arrester operation in case of surge impact and allow preserving the rated insulating strength under the normal operating conditions. In order to confirm the compliance of SAd35z with the required specification, a testing program has been developed. It includes all the main electrical, mechanical and climatic tests (Table 1). 89 IV. POWER ARC FOLLOW (PAF) CURRENT INTERRUPTION V. CHECKING OF ARRESTER COORDINATION WITH DRY INSULATION AND IN THE RAIN IN CASE OF VOLTAGE SURGE WITH A STEEP FRONT TEST The PAF current interruption test was conducted on a high-voltage test bench represented by a high-voltage impulse and current generator which imitates lightning impulse and a generator imitating the grid current of power frequency. Both generators work in parallel (Fig. 3). The lightning generator parameters: current – up to 30kAа (a- amplitude), voltage – 300kVа, duration of current impulse till a half-value – 50 μs. Grid generator has voltage amplitude up to 30kVа with follow current up to 5 kAа (3.5 kAeff of effective value). The coordination is checked to determine the maximum value of spark gap between the intermediate tap leads of shields at which a stable coordinated operation of the arrester complete with the string is observed. The test was conducted in dry conditions and in the rain by voltage surges with the steepness of 2000kV/μs, which are more complicated conditions for the coordinated arrester discharge than a standard lightning impulse. Fig. 3. Principal diagram of test bench In case of direct lightning strike to the phase conductor, lightning current is divided into two parts flowing to the opposite direction from the point of strike. Depending on the lightning current value and tower grounding resistance, arresters installed on the neighboring towers may also operate together with arresters installed on the towers nearest to the strike location. Calculations made in [2] demonstrated that with lightning currents less than 100kA, which happen in 95% of cases, the current passing through the arrester does not exceed 30kA. Fig. 4. Typical voltage and current oscillograms for PAF current quenching at zero point. The testing method was represented by application of impulses with gradual reduction of tap leads length by the method of half-division until the first uncoordinated discharge took place. In the Russian Federation most of OHLs 35kV are operated with three glass insulators in a string, but in certain areas with high pollution level four insulators can be used. Due to the above, the coordination test was conducted on two types of strings (Fig. 5). The arc interruption tests were conducted in three modes with various amplitudes of impulse currents: – high impulse current 30kA of direct lightning strike with t = 8/50 μs; – medium impulse current 10kA of direct lightning strike with t = 8/50 μs; – back flashover mode 2.5 kA with t = 1/50 μs. Impulse current and grid voltage of power frequency 10.5 kVeff were simultaneously applied to each test object (it was a little higher than the necessary level of 10.1 kV eff, mentioned above). Measuring instruments recorded the results – quenching or failure to quench the follow current arc. Each of 12 tested shields demonstrated stable follow current arc interruption at zero level (Fig. 4) in all the variants of pulse current with the stable of MCS mechanical integrity. Fig. 5. Test of SAd35z for discharge coordination 90 U, kV Based on the results of the test, maximum values of spark air gaps between the discharge elements were determined: 220 mm for three-insulator string and 300 mm for four-insulator string. VI. 400 POWER FREQUENCY WITHSTAND VOLTAGE TEST IN DRY AND RAIN CONDITION The test objective is to determine the minimum value of the spark gap with which during one minute of application of power frequency voltage at the level of 80 kV in the rain there is no flashover. The test was conducted by the incremental reduction of the spark gap by increasing tap leads up to the mark of the value preceding the occurrence of the flashover. The minimum value of the spark gap was 10 mm. 300 200 100 Summarizing the results of the coordination test and power frequency withstand voltage test, the mean values of spark gaps (200 mm for three-insulator string and 280 mm for fourinsulator string) with the constant length of coordination tap leads of the upper and lower shields equal to 130 mm have been determined. L, mm 0 440 200 400 570 600 800 Fig. 6. Graph of dependence of 50% discharge voltage on the connecting dimension of SAd35z on strings with three (440 mm) and four (570 mm) insulators. In order to determine a possibility to use SAd35z with types of insulation other than the ones described above, analysis of 50% arrester discharge characteristics was conducted. It was conducted in dry conditions and in the rain at six SAd35z arresters with three- and four-insulator strings using tap leads of constant length. Averaged data of 50% discharge voltages after their processing are presented in Table 2. VII. MEASURING OF INDUSTRIAL RADIO INTERFERENCE LEVEL Initial design of SAd35z supposed the voltage delivery to upper and lower MCS shields via carrying electrodes executed as flat steel rods (Fig. 7а). This solution seemed promising, because it looked simple and significantly increased mechanical strength of the base structure. TABLE 2. 50% DISCHARGE VOLTAGES AT SAD35Z UNDER THE IMPACT OF LIGHTNING-CAUSED OVERVOLTAGES 50% discharge voltage Number of insulators in the string Connecting dimension of SAd35z Three 440 / 200 Four 570 / 280 Insulation condition Positive polarity Negative polarity Dry 190 257 Rain 234 233 Dry 247 359 Rain 314 290 Based on the obtained data, graphs of dependence of 50% discharge voltage on the connecting dimension of SAd35z on strings with three (440 mm) and four (570 mm) insulators were built (Fig. 6). By extending straight lines on the graph in the opposite directions a possibility was obtained to estimate applicability of SAd35z with various types of insulation knowing their 50% discharge voltages and arrester connecting dimensions. On the graph 50% discharge voltages of insulation should be at least 20% above the arrester characteristics. а) b) Fig. 7. Design of input electrodes of SAd35z arrester: a) input electrode without spark gap; b) with spark gap; 1 – steel rod; 2 – intermediate tap leads; 3 – insulation rod; 4 – lower input electrode; 5 – additional spark gap; 6 – traverse; 7 – conductor ; 8 – insulator. However, performed calculations of electric field distribution between the arrester structural elements 91 discovered that when the maximum amplitude voltage of 32.9 kVа is applied thereto, then, in case of high potential input directly in the MCS, the maximum electric field strength occurred at the electrode of the lower shield first chamber, and its value in this point was E ≈ 50kV/cm (Fig. 8а). This significantly exceeded the level of corona ignition of 30kV/cm. With such electric field strength, in several first chambers under the impact of operational voltage partial discharges will continuously occur. They will cause radio interference making not acceptable the initial voltage delivery unit design. shield is impacted by the distributed load of 15 kg. In order to check shield base strength, a withstand load test under the temperature minus 70˚С was conducted in the CNII RTK laboratory. Shields were placed on the compact mountings, which allowed the application of the required distributed load, and this assembly was held for four hours in a climatic chamber under the temperature below 70˚С. Immediately after the chamber opening a two-fold load of 30kg was applied and retained till complete defrosting. The test demonstrated that the shield base material preserved its mechanical strength and elasticity under the impact of 30-kg distributed load, which twice exceeded ice weight with the wall thickness of 40 mm. Reduction of electric field strength at the lower MCS shield to 8kV/cm (Fig. 8 b) is achieved by the provision of the air gap between the MCS and current-carrying accessories (Fig. 7 b). The shield was tested for vibration survival with application of 15-kg distributed load, which imitated a combined impact of wind and ice loads. In order to determine the stiffness level, the analysis of resonance characteristics was conducted according to 100-1 method of GOST 20.57.406-81. In the process of test object resonance characteristics measuring Fres from 30 to 60Hz was revealed with mechanical Q-factor up to 10. Based on the obtained results the sixth degree of stiffness was selected according to GOST 16692.2-90 and a test for vibration survival with the frequency range from 10 to 80Hz was performed with acceleration of 5 m/s² in one direction. The total duration of the test was 6 hours. No damage to shield bases and weakening of fasteners were observed. For the upper shield, which has ground potential, due to the shielding effect of the traverse the electric field strength in the first chamber of the MCS is reduced to the acceptable level of 20kV/cm. Main characteristics of the arrester are provided in Table 3. TABLE 3. MAIN TECHNICAL CHARACTERISTICS OF SAD-35Z ARRESTER Characteristic а) b) Fig. 8. Visualization of electric field intensity in the first three chambers of the lower shield: Value Voltage class, kV 35 Short circuit current effective value, kA 3.5 OHL protection against: direct strikes a) input electrode of the lower shield without spark gap; b) with spark gap. lightning backflashovers Measuring of industrial radio interference level at SAd35z with the arranged spark gap at the lower shield demonstrated that, when the voltage 1.1Ul.op = 44.5 kV is applied, radio interference level was 32 dB (the norm is 55 dB). Minimum commutation life, number of discharges induced overvoltages 10 Diameter of shield with MCS, mm 435 Length of intermediate tap leads, mm 130 Spark gap length with connecting dimensions of: VIII. TEST OF RESISTANCE TO EXTERNAL IMPACT FACTORS Required mechanical characteristics of the shield base are ensured due to use of structural plastic Polyphenylene Sulfide (PPS). This material is used in many industries, including space, automotive, aircraft building, and has a high strength and resistance to aggressive environmental impacts. In the process of SAd35z operation the greatest concern is caused by the mechanical strength of shield base material under the impact of ice load in combination with extremely low value of the ambient temperature. Based on the estimated data, in case of ice wall of 44 mm (the highest degree), one 92 440 mm………………………………… 200 570 mm………………………………… 280 Level of industrial radio interference, dB 32 IX. CONCLUSIONS 1. Multi-chamber shield-type arrester (SAd35z) is designed for 35kV OHL protection against lightning-caused overvoltages, including direct lightning strikes to the conductor; 2. SAd35z is intended for use in the grids with shortcircuit current up to 3.5 kAeff; 3. The arrester is easy to install and operate on OHLs. Implementation doesn’t require insulation replacement; 4. SAd35z successfully passed all electrical and mechanical tests; 5. At the time of this article delivery additional climatic tests for the impact of temperature change, solar radiation and salt fog were not completed. X. REFERENCES: [1] G. V. Podporkin, E. Yu. Enkin, E. S. Kalakutsky, V.E. Pilshikov, A. D. Sivaev. “Overhead Lines Lightning Protection by Multi-chamber Arresters and Insulator-arresters", IEEE Transactions on Power Delivery, vol. 26, No. 1, January 2011, pp.214-221. [2] G. V. Podporkin, E. Yu. Enkin, E. S. Kalakutsky, V. E. Pilshikov and A. D. Sivaev. “Development of Multi-Chamber Insulator-Arresters for Lightning Protection of 220kV Overhead Transmission Lines”, XI International Symposium on Lightning Protection (SIPDA), 3-7 October 2011, Fortoleza, Brazil, Rep. 7-2. 93