ETAP
Project:
12.6.0H
Location:
1
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Page:
Study Case: SC
Config.:
SC2
Normal
Electrical Transient Analyzer Program
Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents
Swing
V-Control
Load
Total
1
1
4
6
XFMR2
XFMR3
Reactor
4
0
0
Synchronous
Power
Generator
Grid
Number of Machines:
2
0
System Frequency:
50.00 Hz
Unit System:
Metric
Project Filename:
SC2
Output Filename:
C:\ETAP 1260\SC2\SC2 Bus 2.SI2
Number of Buses:
Number of Branches:
Line/Cable
Impedance
Tie PD
Total
0
6
2
0
Synchronous
Induction
Lumped
Motor
Machines
Load
Total
0
0
0
2
ETAP
Project:
12.6.0H
Location:
2
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Page:
Study Case: SC
Config.:
SC2
Adjustments
Apply
Tolerance
Individual
Adjustments
/Global
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
Overload Heater Resistance:
No
Transmission Line Length:
No
Cable Length:
No
Apply
Individual
Adjustments
/Global
Transmission Line Resistance:
Yes
Individual
Cable Resistance:
Yes
Individual
Temperature Correction
Percent
Degree C
Normal
ETAP
Project:
12.6.0H
Location:
3
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Page:
Study Case: SC
Config.:
SC2
Bus Input Data
Bus
ID
Type
Initial Voltage
Nom. kV
Base kV
Sub-sys
%Mag.
Ang.
Bus1
SWNG
12.000
12.000
1
100.00
0.00
Bus2
Load
20.000
20.000
1
100.00
30.00
Bus3
Load
20.000
20.000
1
100.00
30.00
Bus4
Load
20.000
20.000
1
100.00
30.00
Bus5
Load
20.000
20.000
1
100.00
30.00
Bus6
Gen.
10.000
10.000
1
100.00
60.00
6 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP .
Normal
ETAP
Project:
12.6.0H
Location:
4
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Page:
Study Case: SC
Config.:
SC2
Normal
Line/Cable Input Data
Ohms or Siemens per 1000 m per Conductor (Cable) or per Phase (Line)
Line/Cable
Length
T (C)
Adj. (m)
% Tol.
Line1
50000.0
0.0
1
75
0.2000000
0.3000000
0.1000000
0.2000000
Line2
30000.0
0.0
1
75
0.2000000
0.3000000
0.1000000
0.2000000
ID
Library
Line / Cable resistances are listed at the specified temperatures.
Size
#/Phase
R1
X1
Y1
R0
X0
Y0
ETAP
Project:
12.6.0H
Location:
Page:
5
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Study Case: SC
Config.:
SC2
Normal
2-Winding Transformer Input Data
Transformer
ID
Rating
Z Variation
MVA
Prim. kV
Sec. kV
%Z
T1
100.000
12.000
20.000
12.50
T2
80.000
12.000
20.000
12.50
T3
60.000
10.000
20.000
T4
50.000
10.000
20.000
X/R
% Tap Setting
+ 5%
- 5%
% Tol.
Prim.
45.00
0
0
0
0
45.00
0
0
0
0
12.50
45.00
0
0
0
12.50
45.00
0
0
0
Adjusted
Sec.
Phase Shift
%Z
Type
Angle
0
12.5000
YNd
0
12.5000
YNd
30.000
0
0
12.5000
YNd
-30.000
0
0
12.5000
YNd
-30.000
30.000
2-Winding Transformer Grounding Input Data
Grounding
Transformer
ID
Rating
Conn.
Primary
Type
kV
Secondary
MVA
Prim. kV
Sec. kV
Type
Amp
Ohm
Type
T1
100.000
12.000
20.000
D/Y
Solid
T2
80.000
12.000
20.000
D/Y
Solid
T3
60.000
10.000
20.000
D/Y
Solid
T4
50.000
10.000
20.000
D/Y
Solid
kV
Amp
Ohm
ETAP
Project:
12.6.0H
Location:
6
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Page:
Study Case: SC
Config.:
SC2
Normal
Branch Connections
CKT/Branch
Connected Bus ID
ID
Type
From Bus
% Impedance, Pos. Seq., 100 MVAb
To Bus
R
X
Z
T1
2W XFMR
Bus1
Bus2
0.27
12.15
12.15
T2
2W XFMR
Bus1
Bus3
0.34
15.19
15.19
T3
2W XFMR
Bus6
Bus4
0.45
20.25
20.25
T4
2W XFMR
Bus6
Bus5
0.54
24.30
24.30
Line1
Line
Bus2
Bus4
250.00
375.00
450.69
Line2
Line
Bus3
Bus5
150.00
225.00
270.42
Y
ETAP
Project:
12.6.0H
Location:
Page:
7
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Study Case: SC
Filename:
Config.:
SC2
Normal
Synchronous Generator Input Data
% Impedance in Machine Base
Synchronous Generator
ID
Rating
Type
MVA
Grounding
Xd"
kV
RPM
% PF
R
Adj.
Tol.
R/X
Xd, sat
Conn.
Type
Excitation
Amp
Type
Gen1
Turbo
70.588
12.000
1500
85.00
1.000
19.00
0.0
0.05
155.00
Wye Solid
0.00
Turbine 130%
Gen2
Turbo
58.824
10.000
1500
85.00
1.000
19.00
0.0
0.05
155.00
Wye Solid
0.00
Turbine 130%
Total Connected Synchronous Generators ( = 2,00 ) : 129,412 MVA
ETAP
Project:
12.6.0H
Location:
Page:
8
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Study Case: SC
Filename:
Config.:
SC2
Normal
SHORT- CIRCUIT REPORT
Fault at bus:
Nominal kV
Voltage c Factor
Bus2
= 20.000
= 1.10 (User-Defined)
Contribution
From Bus
3-Phase Fault
To Bus
ID
ID
%V
kA
From Bus
Positive & Zero Sequence Impedances
Looking into "From Bus"
Line-To-Ground Fault
% Voltage at From Bus
Symm. rms
Va
Vb
kA Symm. rms
Vc
% Impedance on 100 MVA base
Ia
3I0
R1
11.797
11.797
3.12E+000
3.49E+001
X1
4.45E-001
R0
1.17E+001
X0
Bus2
Total
0.00
9.051
0.00
89.65
86.63
Bus4
Bus2
85.70
0.604
86.96
95.60
98.94
0.672
0.464
2.57E+002
4.59E+002
1.25E+002
2.70E+002
Bus1
Bus2
32.54
8.504
59.76
63.56
98.63
11.183
11.371 *
2.24E+000
3.73E+001
2.70E-001
1.21E+001
Bus6
Bus4
88.98
0.604
91.54
99.76
94.47
0.672
0.464 *
6.93E+000
8.38E+001
4.50E-001
2.02E+001
Bus3
Bus1
35.21
0.985
45.08
90.10
86.59
0.734
0.000
1.24E+002
3.71E+002
Gen1
Bus1
100.00
13.253
100.00
100.00
100.00
9.969
0.000
1.42E+000
2.69E+001
1.42E+000
9.92E+000
Initial Symmetrical Current (kA, rms)
:
Peak Current (kA), Method C
:
3-Phase
9.051
23.334
Breaking Current (kA, rms, symm)
Steady State Current (kA, rms)
:
:
9.051
L-G
11.797
30.412
11.797
11.797
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
L-L
7.964
20.530
L-L-G
11.493
29.629
7.964
7.964
11.493
11.493
ETAP
Project:
12.6.0H
Location:
Page:
9
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Study Case: SC
Filename:
Config.:
SC2
Fault at bus:
Nominal kV
Voltage c Factor
Normal
Bus6
= 10.000
= 1.10 (User-Defined)
Contribution
From Bus
3-Phase Fault
To Bus
ID
ID
%V
kA
From Bus
Positive & Zero Sequence Impedances
Looking into "From Bus"
Line-To-Ground Fault
% Voltage at From Bus
Symm. rms
Va
Vb
kA Symm. rms
Vc
Ia
3I0
% Impedance on 100 MVA base
R1
X1
Bus6
Total
0.00
22.427
0.00
89.43
88.79
28.280
28.280
3.04E+000
2.82E+001
Bus4
Bus6
3.74
1.174
50.85
53.58
98.17
0.966
0.000
2.56E+002
4.76E+002
Bus5
Bus6
7.06
1.845
50.77
55.25
98.20
1.518
0.000
1.53E+002
3.09E+002
Gen2
Bus6
100.00
19.636
100.00
100.00
100.00
25.956
28.280
1.70E+000
3.23E+001
Bus2
Bus4
86.52
0.587
93.77
89.81
99.74
0.423
0.000
1.72E+001
5.20E+002
Bus3
Bus5
84.60
0.922
92.95
88.29
99.72
0.665
0.000
2.26E+001
3.19E+002
Initial Symmetrical Current (kA, rms)
:
Peak Current (kA), Method C
:
3-Phase
22.427
56.709
Breaking Current (kA, rms, symm)
Steady State Current (kA, rms)
:
:
22.427
L-G
28.280
71.509
19.873
50.250
L-L-G
26.734
67.599
28.280
19.873
26.734
28.280
19.873
26.734
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
L-L
R0
X0
1.70E+000
1.19E+001
1.70E+000
1.19E+001
ETAP
Project:
12.6.0H
Location:
10
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Page:
Study Case: SC
Config.:
SC2
Normal
Short-Circuit Summary Report
3-Phase, LG, LL, LLG Fault Currents
Bus
ID
3-Phase Fault
kV
I"k
ip
Line-to-Ground Fault
Ik
Ib
Ik
20.000
9.051
23.334
9.051
11.797
30.412
11.797
11.797
7.964
20.530
7.964
7.964
11.493
29.629
11.493
11.493
Bus6
10.000
22.427
56.709
22.427
28.280
71.509
28.280
28.280
19.873
50.250
19.873
19.873
26.734
67.599
26.734
26.734
* LLG fault current is the larger of the two faulted line currents.
ip
Ib
Ik
I"k
ip
*Line-to-Line-to-Ground
Bus2
All fault currents are in rms kA. Current ip is calculated using Method C.
I"k
Line-to-Line Fault
I"k
ip
Ib
Ik
ETAP
Project:
12.6.0H
Location:
11
Date:
24-10-2020
SN:
Contract:
Revision: Base
Engineer:
Filename:
Page:
Study Case: SC
Config.:
SC2
Normal
Sequence Impedance Summary Report
Bus
ID
Positive Seq. Imp. (ohm)
kV
Resistance Reactance Impedance
Negative Seq. Imp. (ohm)
Zero Seq. Imp. (ohm)
Resistance Reactance Impedance
Resistance Reactance Impedance
Fault Zf (ohm)
Resistance Reactance Impedance
Bus2
20.000
0.12475
1.39773
1.40328
0.16548
1.34947
1.35958
0.01779
0.46815
0.46849
0.00000
0.00000
0.00000
Bus6
10.000
0.03037
0.28154
0.28318
0.04240
0.26717
0.27052
0.01700
0.11899
0.12020
0.00000
0.00000
0.00000